Because of the heating effect in compact enclosures, the 100A versions should be downrated to 85A when in continuous operation
Auxiliary contact < 333-546') 333-546/ should not be used with switches above 100A operating current
Switch power/capacity refers to AC23A use at 380-440V
Accessories shown in this module only suitable for use with P series switch disconnectors
Switch Disconnectors with Auxiliary Contacts
For use on single-speed single direction motors Sheet steel enclosures, ingress protection to IP65 Supplied with 1 x N/O and 1 x N/C auxiliary contact (20A 3 pole one N/O contact only) Lockable in off position with up to three padlocks Cover interlocked in the ON position